Technical Specifications  
V100P V100E
Input range: 3-15 PSI (20-100kPa) 4-20mA (R1<25ohms)
Supply pressure: <145 PSI (<1MPa) 21.8-145 PSI (0.15-1MPa)
Linearity error: <0.7% f.s. <1.0% f.s.
Hysteresis: <0.4% f.s. <0.6% f.s.
Repeatability: <0.3% f.s. <0.5% f.s.
Pressure Gain:
@87 PSI (600kPa)
750 Pout / Pin
acc. to ISA S75.13
49% Pout / %Pin
Air Capacity: SCFM (SLPM)
@29 PSI (200kPa) 9.5 (270)
@87 PSI (600kPa) 28.3 (800)
@145 PSI (1MPa) 47.1 (1350)
Bleed Rate: SCFM (SLPM) SCFM (SLPM)
@29 PSI (200kPa) 0.18 (5) 0.2 (5.7)
@87 PSI (600kPa) 0.53 (15) 0.6 (17.0)
@145 PSI (1MPa) 0.88 (25) 1.0 (28.3)
Temperature range: -40° to 185° Fahrenheit
-40° to +85° Celsius
Air connectors: 1/4" NPT (optional G threads)
Gauges: 1/8" NPT (optional G threads)
Cable entry: 1/2" NPT (optional M20x1.5 or PG 13.5)
Ingress & corrosion protection: NEMA 4X and IP66
Coating: Powder Polyester
Weight: 3.5 lbs (1.6kg) 3.8 lbs (1.7kg)
Weight with gauges: 4.0 lbs (1.8kg) 4.2 lbs (1.9kg)
Options:
Feedback Spring for 6-30PSI (40-200kPa) input signal
Gauges
Various cams

Pilot Valves:
Type W1 for better stability and lower bleed. Pressure gain @ 87 PSI = 300
Bleeds 33% less but has 10 % less air capacity than standard valve W3.

Type W2 for faster response and better accuracy. Pressure gain @87 PSI > 1000
Has same air capacity but bleeds 33% more than standard valve W3.

Above specifications are based on Type W3 as the standard pilot valve.

Ordering Codes
Positioner Type Drive Front Cover Indicator Cam
V100 P-Pneumatic D1-Namur 90-90 degree A-arrow C1-Standard-90°
E-Electropneumatic D2-1/2" square 60-60 degree B-raised C2-60° & 30°
EX-Explosion Proof (others available) 45-45 degree C3-45° & 90°
FF-Fail Freeze 30-30 degree C4-120° & 60°
Example: V100E-D1-90-B-C1
Electropneumatic positioner, with namur drive, 90° cover, raised indicator, and standard 90° cam.
BLX Feedback Module

The BLX R100 (positioner mounting) and the R300 (stand alone) feedback modules allow for accurate position feedback, where on-off indication (mechanical switches) or 4-20mA transmitter or potentiometer is required. Feedback unites can be factory or field mounted to the V100 positioner with no additional parts or mounting brackets required, thus creating a very compact package. Combination of switches and transmitters or potentiometer are available. The positioner/switch package is completely sealed, and can be fitted with a flat or raised indicator. Spring-loaded switches and transmitter make calibration simple and quick.


BLX Feedback Module Jumpers

Specifications:

  • Output 4-20mA, 2 wire
  • Voltage supply 10-30VDC
  • Loop Impedance: max 700ohms @ 24 VDC
  • Temp. range -40°F to +185°F (-40°C to +85°C)
  • Unlinearity <1.5%
  • Hysteresis <0.3%
  • Temp. Sensitivity <0.1% / 10°F(5.5°C)
  • Enclosure NEMA 4X (IP66)
  • Painting: Powder polyester
  • 2 Conduit connections 1/2" NPT
  • Internal and external grounding points
  • Bold on to BLX V100 positioner without any mounting details

Settings on PC-board

  • Jumper for Direct(CCW) or Reverse (CW) rotation
  • mper for 45 detings on PC-board
  • Jumper for Direct(CCW) or Reverse (CW) rotation
  • Zero fine set by means of set potentiometer +/- 10%
  • Zero Coarse set by means of simple gear teeth adjustment
  • Test pins for easy calibration in loop

Electronics are short circuit protected

Ordering Codes
Type Switch Feedback Front Cover
(R300 only)
Indicator
(R300 only)
R100-Feedback Module M-Mechanical (2 spdt) mA-4/20mA 90-90 degree A-Arrow
R100-Positioiner Mounted R-Reed (2 spdt) P1-1k Pot 60-60 degree B-Raised
R300-Feedback Module N-Namur P5-5k Pot 45-45 degree
R300-Stand Alone 30-30 degree

Available with switches only, transmitter or pot only, or combinations of switches and transmitter or switches and pot.
R100 utilizes positioner front cover.

Example: R100-M-mA
Feedback module with 2 mechanical switches, 4-20 mA transmitter.